Enter pipe size, material, design flow, and drainage type to calculate hydraulic fall or full-flow capacity and screen eligible foul-drain conditions against Approved Document H Table 6.
For educational purposes only. Not a substitute for professional engineering judgment.
Choose whether to calculate required gradient or flow capacity
Table 6 screening applies to foul drains only; surface-water results are hydraulic
Mapped from supported product diameters; confirm the pairing against product data
Required because the flatter Table 6 rows are conditional on WC count
Select pipe size in millimetres
Select material to determine Manning's roughness coefficient
Leave blank to use default for selected material
Used for the Manning calculation, capacity check and Table 6 flow band
Drainage fall (also called gradient or slope) is the vertical drop of a pipe over its horizontal length — what makes a gravity drain flow. Choose a mode above:
For foul drains, Table 6 is assessed only when the peak-flow, nominal pipe-size and WC conditions match a published row. Surface-water and unmatched cases remain hydraulic results without a Part H compliance claim.
| Pipe | Peak flow | Typical minimum gradient | Condition / capacity |
|---|---|---|---|
| 75mm | <1 l/s | 1:40 | 4.1 l/s maximum capacity |
| 100mm | <1 l/s | 1:40 | 9.2 l/s maximum capacity |
| 75mm | >1 l/s | 1:80 | 2.8 l/s maximum capacity |
| 100mm | >1 l/s | 1:80 | Minimum 1 WC; 6.3 l/s at 1:80 |
| 150mm | >1 l/s | 1:150 | Minimum 5 WCs; 15.0 l/s capacity |
Exact rows and conditions from Approved Document H Table 6 for foul drains. The 100mm >1 l/s row is 1:80 (not 1:100). Table 6 does not provide a blanket surface-water minimum. Confirm nominal product size and the current document with building control.